| Specifications
1. Input: 24VDC, no sensor
30 ma, with sensor up to 2A.
2. Excitation Power: 24VDC up to 2A.
3. Analogue Input: 0-20 ma, 4-20 ma, 0-10 VDC, 2-10
VDC
4. Signal Input Resistance: (Voltage Input 100K Ohms)
(Current Input 250 Ohms)
5. Set Point Range: (0-10 VDC) (0-20mA)
6. Set Point Hysteresis 1%
7. Signal Averaging (Voltage Input 0-1s per volt) (Current
Input 0-.5s per ma
8. Analogue Output: 0-10VDC with load resistance 1K
to infinity
9. Relay Contacts: (Resistive Load, 2A@277AC and 3A@
30VDC/125VAC)
10. Relay Contacts: (Inductive Load, 1A@125VAC)
11. Relay Switching Min: (Current 10mA) Max (Voltage
30VDC/277VAC)
12. Operating Temperature Range: -25 to 70 C or -13
to 158 F
13. Humidity: 0 to 95% Non-Conducting
|
Terminals
Set Point Side
1. 0-20 ma In
2. 0-10 Volts In
3. 24 VDC out
4. GND (sensor ground)
5. Feed through
Relay Output Side
1. N.C. Relay Contact
2. N.O. Relay Contact
3. Relay Com
4. Feed through
5. +24 VDC Power In
6. GND (power ground)
7. 0-10 analogue out
|