| The SPC-704 is an
adjustable controller with 4 setpoints. The 4 setpoints
are independently adjusted, each having a Form C relay
output. This controller can be used with any sensor or
device that produces 0-20mA, 4-20mA, 0-10V, or 2-10V analogue
output. The SPC-704 will work with all Migatron analogue
output sensors. Besides the 4 relay outputs, there is
one 0-10V analogue output. This can be used to drive a
meter or other analogue drive controls. This analogue
output can also feed a second SPC-704 to produce additional
outputs. The SPC-704 also provides 24 VDC excitation power
at 150 mA to drive input sensors. The SPC-704 has a signal
averaging potentiometer that helps alleviate false trips
during sudden signal changes. |
|
Mechanically, the
SPC-704 is made out of sturdy (UL 94) approved materials.
The controller is DIN rail mountable. The terminal blocks
are removable for easy wiring. There are easy to view
bright LEDs that show the relay status. The SPC-704 comes
in two versions, 115 VAC or 230 VAC*. If AC power
is not available both versions can also be powered by
24 VDC. The relay outputs can handle up to 3 amps. |
| Specifications
1. Power Input: 115 or 230
VAC 50/60 Hz @ 9VA / 24VDC @ 225mA
2. Excitation Power: 24VDC @ 150mA
3. Analogue Input: 0-20 ma, 4-20 ma, 0-10 V, 2-10 V
4. Signal Input Resistance: (Voltage Input 100K Ohms)
(Current Input 250 Ohms)
5. Set Point Range: (0-10 VDC) (0-20mA)
6. Set Point Hysteresis 1%
7. Signal Averaging (Voltage Input 0-1s per volt)
(Current Input 0-.5s per ma)
8. Analogue Output: 0-10VDC minimum load resistance
1K
9. Relay Contacts: (Resistive Load, 1A@125VAC)
10. Relay Contacts: (Inductive Load, 1A@125VAC)
11. Relay Switching Min: (Current 10mA) Max (Voltage
30VDC/277VAC)
12. Operating Temperature Range: -20 to 55 C or -4 to
131 F
13. Humidity: 0 to 95% Non-Conducting
14. Enclosure: Thermoplastic (UL 94 V2 and V4 material)
|
Terminals
Potentiometer Side
1. 24 VDC out
2. GND (sensor ground)
3. 0-10 Volts In
4. 0-20 ma In
5. 0-10 analogue out
6. GND
7. 24 VDC Power In
Relay Output Side
* 2. Line VAC 115 or 230 VAC Power In Line
PLEASE SPECIFY VOLTAGE WHEN ORDERING
3. Neutral
4. Earth Ground
5 Through 16 are relay connections
|